Tall Trees Water
Water Systems Operation Report
Microbiological Sample Results
Submitted By: CAMO Pollution Control, Inc.
1610 Route 376
Wappingers Falls, New York 12590
Name of Public Water System Program Code Federal Reporting MonthlYear
Tall Trees Water 100 1302809 December 2004
Location:
TOWN OF WAPPINGER
Source of Supply:
If surface, is filtration provided?
Did an emergency occur in any part of the water system?
Does the system have a disinfection waiver?
CHLORINATION
Amount of Gaseous L1auld
Treated Chlorine Hypo- Frea
Water Weight of Used chlorite Chlorine
Date 1.000 Gals. Cylinder Lbs.per Used Residual pH
Per Day Lbs. 24 Hrs. Qts. mg/1
1 20.50 28 0.9
2 20.60 28 1.0
3 19.70 32 1.0
4 16.80 28 1.0
5 20.50 28 1.2
6 20.80 28 1.0
7 18.60 24 1.1
8 20.00 22 1.0
9 19.10 24 0.9
10 18.10 28 1.0
11 20.60 32 0.9
12 22.60 26 1.2
13 17.30 14 1.1
14 21.00 24 1.0
15 20.60 24 1.0
16 17.10 26 1.0
17 19.20 28 1.1
18 20.40 34 1.0
19 21.90 32 1.2
20 21.10 32 1.3
21 19.70 28 1.0
22 19.10 24 0.9
23 26.20 40 1.1
24 19.70 32 1.0
25 20.50 26 1.0
26 20.50 26 1.0
27 22.40 30 1.3
28 20.50 28 1.2
29 20.00 28 0.8
30 22.10 28 1.0
31 25.00 36 0.8
Total 607 868 32
Avg. 20.39 28.0 1.0
County:
DUTCHESS
I Ground I ~~
Population served: 251
Number of required routine samplE 1
Number of actual routine samples 1
Does a M&AR violation exist? NO
If yes, check reason(s) below:
_ Actual number of samples fewer than required.
_ Failure to analyze for E.colllf there was a
positive result for total coliforms from routine. repeat or
high turbidity (hiturb) sample?
_ Failure to analyze repeat samples.
Does an MCL violation exist? NO
If yes, check reason(s) below:
_ Two or more positive total coliform samples for
systems collecting fewer than 40 samples (routine, repeat
or hiturb) per month.
_ More than 5% positive total coliform samples for
systems collecting 40 or more samples (routine, repeat or
hiturb) per month.
_ When a positive total Coliform sample is positive
for E.coll and a repeat Total Coliform sample Is positive,
OR. when a positive Total Coliform semple is negative for
E.coll, but the repeat Total Coliform sample Is positive and
also is positive for E.coIi.
. Must collect a minimum of 5 routine samples the month
following a repeat sample collection.
Reported by: CAMO Pollution Control, Inc.
Title: Operator
Date: ;/1 ( / () 5
.
~.'-----
Grade Level: itA
Cert.No. 12947
Distribution System Analytical Results
Sampling Date of Sample Total Coliform E.coli Free CI- Raw
Location Sample Type Positive Positive Residual Turbidity
(1,2,3)* mg/L NTU
P.O.E 12/10/04 1 No No 0.5 -
-
Yes No Yes No - - - -
Yes No Yes No - - - -
Yes No Yes No - - - -
Yes No Yes No - - - -
Yes No Yes No - - - -
Yes No Yes No - - -
-
Yes No Yes No - - - -
Yes No Yes No - - - -
Yes No Yes No - - -
-
Yes No Yes No - - -
-
Yes No Yes No - - -
-
Yes No Yes No -
- - -
Yes No Yes No - - -
-
Yes No Yes No -
- - -
Yes No Yes No - - -
-
Yes No Yes No -
- - -
Yes No Yes No -
- - -
Yes No Yes No -
- - -
*1 = Routine sample 2 = Repeat sample 3 = Hiturb sample
COMMENTS and/or REMARKS
ENVIRONMENTAL LABWORKS, INC.
BOTTLE NUMBER
t... { ()r;) t J (
COLLECTED BYJ J.. J
EXACT COLLECTION POINT
ol,t.;;e/Z-
NAMe ANOiOR LOCATIONS OF WATER SOURCE:
.--.-
P.O. Box 733, Marlboro, N_York 12542
(845) 236-7823
Fax (845) 236-3911
ELAP 10# 10824
PRIVATE SUPPLY Q
REPORT TO BE MAJU:D TO
BACTERIOLOGICAL EXAMINA liON OF WATER
"J-. -...
- - -.. -.j,
" ?f?llJ
_..,I....,-q.
RESULTS OF EXAMINATION
BACTERIA I lolL AT :J5oC
TOTAl CClLFOAMS 11Clll101t.
ABSENT
METHOD OF EXAMINATION
PIA C MPN C MF C CoIIIert
OTHER TESTS
REMARKS
INTERPRETATION OF RESULTS
TIiESE RESULTS INDICAn TIiATTIiE WATER WAS
IN RESPECl' TO THE ABOVE TEST, WHEN
REPORTED BY
OF A SATISFACTORY SANITARY QUALITY
WAS ANALVZED..
DATE
z.. c=, 0