Wappingers Park Water
"
,It
o \.f
Water Systems Operation Report
Microbiological Sample Results
Submitted By:
C'/!J"O Pollution Control, Inc.
1610 Route 376
Wappingers Falls, New York 12590
Name of Public Water System Program Code Federal Reporting MonthNear
Wappigners Park Water 100 1302782 October 2004
Location:
TOWN OF WAPPINGER
Cou nty:
DUTCHESS
I~~
Source of Supply:
If surface, is filtration provided?
Did an emergency occur in any part of the water system?
Does the system have a disinfection waiver?
I Ground
CHLORINATION
Amount of Gaseous Liquid
Treated Chlorine Hypo- Free
Water Weight of Used chlorite Chlorine
Date 1,000 Gals. Cylinder Lbs. per Used Residual pH
Per Day Lbs. 24 Hrs. Qts. mgJl
1 15.80 44 1.3
2 15.20 38 0.8
3 19.20 48 0.2
4 18.80 50 0.4
5 20.50 52 1.0
6 15.40 38 1.0
7 15.70 44 1.1
8 28.30 52 1.0
9 15.90 40 1.1
10 22.70 64 1.5
11 19.20 48 1.0
12 15.40 38 1.7
13 17.50 46 1.5
14 16.80 46 1.7
15 16.40 44 1.0
16 17.40 48 1.0
17 19.90 56 0.8
18 19.60 56 1.0
19 14.20 38 2.0
20 18.90 50 1.5
21 14.60 44 1.0
22 19.30 56 0.8
23 19.40 56 1.2
24 18.40 56 1.2
25 0.3
26 0.6
27 0.4
28 0.4
29 0.4
30 0.3
31 0.4
Total 91,515 1,152 29
Avg. 14.48 48.0 1.0
Population served:
400
Number of required routine samplE R E C
Number of actual routine samples
NOV
1
;;.
"t
Does a M&AR violation exist? S l ! ~<t (:)'
If yes, check reason(s) below: .. ..,.
_ Actual number of samples fewer than required.
_ Failure to analyze for E.coli if there was a
positive result for total coliforms from routine, repeat or
high turbidity (hiturb) sample?
_ Failure to analyze repeat samples.
Does an MCL violation exist? NO
If yes, check reason(s) below:
_ Two or more positive total coliform samples for
systems collecting fewer than 40 samples (routine, repeat
or hiturb) per month.
_ More than 5% positive total coliform samples for
systems collecting 40 or more samples (routine, repeat or
hiturb) per month.
_ When a positive total Coliform sample is positive
for E.coli and a repeat Total Coliform sample is positive,
OR, when a positive Total Coliform sample is negative for
E.coli, but the repeat Total Coliform sample is positive and
also is positive for E.coli.
. Must collect a minimum of 5 routine samples the month
following a repeat sample collection.
Reported by: CAMO Pollution Control, Inc.
Date: / J /rs/O L{
I
Q: ,~a~~ Q_
Grade Level: IIA
Title: Operator
Cert. No. 12947
Wappinger Park water connected to Central Wappinger Water on 10/25/04
RESULTS OF EXAMINATION
..
...
\..;
'wi
. ENVIRONMENTAL LABWORKS, INC.
P.O. Box 733, MaI1boro. New York 12542
(845) 236-7823
Fax (845) 236-3911
ELAP 10# 10824
BACTERIOLOGICAL EXAMINATION OF WATER
REPORT TO BE MAn..EO TO
(2~
BACTERIA I lolL AT 35-C
TOTAl COlIFORMS I 100Ml
ABSENT
METHOD OF EXAMINATION
PIA C MPN C MF C CoIi1ertjEJ
OTHER TESTS
PWSID# 130 ;l
CHLORINATED .
NO C YES.p\ ppmO.&
REMARKS
. INTERPRETATION OF RESULTS
THESE RESULTS INDICA TJ:~ THAT THE WATER WAS
IN RESPECT TO nm ABOVE TEST, WHEN
OF A SATISFACfO\<Y SANITARY QUALITY
LEWAS ANALYZED..
REPORTED BY
DATE