Wappingers Park Water
CHLORINATION
Amount of Gaseous Liquid
Treated Chlorine I Hypo- Free
Water Weight of Used I chlorite Chlorine
, pH
Date 1,000 Gals. Cylinder Lbs. per I Used Residual
Per Day Lbs. 24 Hrs. Ots. mgll
1 20.80 40 1.0 7.2
2 14.20 24 0.5 7.2
3 24.10 44 1.0 7.2
4 20.10 36 0.6 7.2
5, 18.40 36 0.3 7.2
61 18.90 24 0.4 7.2
7 20.80 40 0.6 7.2
8 27.50 50 0.6 7.2
9 24.40 48 0.5 7.2
10 16.80 32 0.3 7.2
11 19.30 36 0.5 7.2
12 18.90 36 0.8 7.2
13 19.10 32 1.0 7.2
14 11.90 28 0.5 7.2
15 24.40 48 1.0 7.2
16 23.90 I 48 1.0 7.2
17 21.20 I 44 0.3 7.2
18 I 17.50 32 0.5 7.2
19 18.20 36 0.7 7.2
20 i 15.00 36 1.0 7.2
I 21 i 12.00 28 0.7 7.2
I
22 24.10 46 1.0 7.2
23 19.50 40 1.2 7.2
24 16.00 32 0.8 7.2
25 16.20 32 0.8 7.2
26 13.40 28 0.6 7.2
I 27 16.50 32 0.4 7.2
K81 18.30 i 34 0.2 7.2
29 12.40 24 1.0 7.2
30 22.70 44 1.0 7.2
I 31 I
Total 567 1,090 21 216 i
Avg. 18.27 36.3 0.7 7.2
.-
Water Systems Operation Report
Microbiological Sample Results
Name of Public Water System
Program Code
Wappingers Park Water
100
Location:
TOWN OF WAPPINGER
Source of Supply:
If surface, is filtration provided?
Did an emergency occur in any part of the water system?
Does the system have a disinfection waiver?
Reported by: CAMO Pollution Control, Inc.
Title: Operator
Submitted By: CAMO Pollution Control, Inc.
1610 Route 376
Wappingers Falls, New York 12590
Federal Reporting MonthNear I
!
1302782
September 2001
County:
DUTCHESS
Ground
No
No
No
Population served: 400
Number of required routine sampl 1
Number of actual routine samples 1
Does a M&AR violation exist? NO
If yes, check reason(s) below:
_ Actual number of samples fewer than required.
_ Failure to analyze for E.coli if there was a
positive result for total coliforms from routine. repeat or
high turbidity (hiturb) sample?
_ Failure to analyze repeat samples.
Does an MCL violation exist? NO
If yes, check reason(s) below:
_ Two or more positive total coliform samples for
systems collecting fewer than 40 samples (routine, repeat
or hiturb) per month.
_ More than 5% positive total coliform samples for
systems collecting 40 or more s.amPlesRutine, repeat or
hiturb) per month. C~\"E.\J
_ Wha'€!tiV; total xOlj~~'amPle is positive
for E.coli and a rep~rT~al Colftorm sample is positive,
OR, when a positive'Total Coliform sa~\,negative for
E.coli, but the repeat T~~tGb'Jiip'e is positive and
also is positive for E~'ttJ '\I ~. .
. Must collect a minimum of 5 routine samples the month
following a repeat sample collection.
Date: /0/0/0,
I
~ ^-~~
\
Grade Level: IIA
Cert. No. 12947
ENVIRONMENTAL LABWORKS, INC.
PO Box 733, Mar1boro, New Yorl<: 12542
(845) 236-7823
Fax (845) 236-3911
ELAP 10# 10824
-j f')
1 ::. ZnOl'
BOTTLE NUUBER
BACTERIOLOGICAL EXAMINATION OF WATER
DATE AND TIM.E RECEIVED
'1 II J/r; I d-P n.
SAUPlE COllECTED FROt.I
PUBUC SUPPLY
CHLORINATED
NO 0 YES 0 ppmO - S-
BACTERIA /Ml AT 35-C
TOT At COUFORI.CS /lOO1olL
ABSENT
OTHER TESTS
REMARKS
INTERPRETATION OF RESULTS
t.IETHOO OF EXAMINATION
PIA 0 MPN 0 MF 0 Colilert IX
THESE RESULTS INDICATE THAT THE WATER
IN RESPECT TO THE ABOVE TEST,
WAS
OF A SATISFACTORY SANITARY QUALITY
LE WAS ANALYZED.
REPORTED BY
DATE