Atlas Water Facility
i
Water Systems Operation Report
Microbiological Sample Results
Submitted By: CAMO Pollution Control, Inc.
1610 Route 376
Wappingers Falls, New York 12590
Program Code Federal Reporting MonthNear
I Name of Public Water System
I'
Atlas Water Facility
Location:
100
TOWN OF WAPPINGER
Source of Supply:
If surface, is filtration provided?
Did an emergency occur in any part of the water system?
Does the system have a disinfection waiver?
I Amount of I CHLORINATION I
Gaseous Liquid
I Treated ! Chlorine Hypo- Free ,
: Water Weight of I Used chlorite Chlorine
Date11'000 Gals. Cylinder Lbs.per Used Residual pH
Per Day Lbs. 24 Hrs. Qts. mgll
1 219.60 148 0.4 7.4
2 211.00 124 0.4 7.4
3 240.10 136 0.4 7.4
4 271.40 148 0.4 7.4
5 248.40 140 0.4 7.4
6 205.90 116 0.6 7.4
7 239.30 132 0.4 7.4
8 224.40 124 0.4 7.4 I
9 171.90 96 0.4 7.4
10 245.40 152 0.4 7.4
11 273.90 150 0.4 7.4
12 226.30 128 0.4 7.4
13 209.30 124 0.4 7.4
14 242.40 I 120 0.4 7.4
~15 226.60 124 0.4 7.4
16 172.50 100 0.4 7.4
, 17 236.60 144 0.4 7.4
18 235.00 128 0.4 7.4
19 283.10 I 164 0.4 7.4
I 20 225.80 132 0.4 7.4
I 21 177.90 104 0.5 7.4 ,
22 211.70 120 0.4 7.4'
23 174.00 132 0.4 7.4
I 24 236.10 132 0.4 7.4
! 25! 278.70 156 0.4 7.4
i 26 227.30 , 132' 0.4 7.4 I
!
I 27 244.20 140 0.4 7.4
28 209.40 i 116 0.4 7.4
29 I
30
31 i I !
I
,
! Total I 6,368
I Avg. 1 227.44
Reported by:
Title:
I
Date: S~/o I
81~
3,6621
130.81
12,
0.41
CAMO Pollution Control, Inc.
Operator
1302789
February
2001
County:
DUTCHESS
Ground !
No
No I
No I
Population served: 1,800
Number of required routine sampl 2
Number of actual routine samples 2
Does a M&AR violation exist? NO
If yes, check reason(s) below:
_ Actual number of samples fewer than required.
_ Failure to analyze for E.coli if there was a
positive result for total coliforms from routine, repeat or
high turbidity (hiturb) sample?
_ Failure to analyze repeat samples.
Does an MCL violation exist? NO
If yes, check reason(s) below:
_ Two or more positive total coliform samples for
systems collecting fewer than 40 samples (routine, repeat
or hiturb) per month.
_ More than 5% positive total coliform samples for
systems collecting 40 or more samples (routine, repeat or
hiturb) per month.
_ When a positive total Coliform sample is positive
for E.coli and a repeat Total Coliform sample is positive,
OR, when a positive Total Coliform sample is negative for
E.coli, but the repeat Total Coliform sample is positive and
also is positive for E.coli.
. Must collect a minimum of 5 routine samples the month
following a repeat sample collection.
Grade Level: IIA
Cert. No. 12947
Distribution System Analytical Results
Sampling Date of Sample Total Coliform E.coli Free CI- Raw
Location Sample Type Positive Positive Residual Turbidity
(1,2,3)* mg/L NTU
Wildwood Laundry 02/20/01 1 No No 0.3 .
POE 02/20/01 Yes No Yes No 0.4
Yes No Yes No
Yes No Yes No
Yes No Yes No
Yes No Yes No
Yes No Yes No
Yes No Yes No
Yes No Yes No
Yes No Yes No
Yes No Yes No
Yes No Yes No
Yes No Yes No
Yes No Yes No
Yes No Yes No
Yes No Yes No
Yes No Yes No
Yes No Yes No
Yes No Yes No
*1 = Routine sample 2 = Repeat sample 3 = Hiturb sample
COMMENTS and/or REMARKS
ENVIRONMENTAL LABWORKS, INC.
P.O. Box 733, Martboro, New York 12542
(845) 236-7823
Fax (845) 236-3911
ELAP 10# 10824
R E eEl V E 0 MAR - 1 ZOOt
BOTTLE NUMBER
BACTERIOLOGICAL EXAMINATION OF WATER
PWSID# /3 o~7g )
ppm l).,J
REPORT TO BE M
RESULTS OF EXAMINATION
~b l CJ
t.QP
~
~c>u'tE '576
I 1,j y \ -z.,S 9-a
TOT....L COLlFORMS /l00ML OTHER TESTS
ABSETN ~~
REMARKS
BACTERIA J ML ....T 35-C
METHOO OF EXAMIN....TION
. INTERPRETATION OF RESULTS
PIA 0 MPN 0 MF 0 Colilert ~
REPORTED BY
OF A SATISFACTORY SANITARY QUALITY
E WAS COLLECTED.
THESE RESULTS INDICATE THAT THE WATER
IN RESPECT TO THE ABOVE TEST, WHEN
ENVIRONMENTAL LABWORKS, INC.
BOTTLE NUt.4BER
REtE I" ED MAR.. 1 lOOf
BACTERIOLOGICAL EXAMINATION OF WATER
P.O. Box 733, Marlboro, New York 12542
(845) 236-7823
Fax (845) 236-3911
ELAP 10# 10824
DATE AND TIME RECEIVED
20 2.: 70
el/
TELEPHONE #
PRIVATE SUPPLY 0
REPORT TO BE MAIL~O
RESULTS OF EXAMINATION
\blD
\J..::J?
~tt '07b
~'( l2b~O
BACT.ER1A I Ml AT 35-C
TOTAL COllFORMS /100ML
OTHER TESTS
REMARKS
ABSENT
METHOD OF EXAMINATION
_ INTERPRETATION OF RESULTS
PIA 0 MPN 0 MF 0 Colilert ~
REPORTED BY
OF A SATISFAcroRY SANITARY QUALITY
WAS COLLECTED.
THESE RESULTS INDICA TF. THAT THE WATER
IN RESPECT TO mE ABOVE TEST,
ATE