Robinson Lane
Submitted By: CAMO Pollution Control, Inc.
1610 Route 376
Wappingers Falls, New York 12590
Federal Reporting MonthNear I
1330219 June 20101
Water Systems Operation Report
Microbiological Sample Results
I:me of Public Water System
ROBINSON LANE
Program Code
100
Location:
TOWN OF WAPPINGER
County:
DUTCHESS
Source of Supply:
If surface, is filtration provided? No
Did an emergency occur in any part of the water system? No
Does the system have a disinfection waiver? No
l 1 CHLORINATION
I Amount of Gaseous Liquid
I Treated Chlorine Hypo- Free
I I Water Weight of Used chlorite Chlorine
~ate 1,000 Gals, Cylinder Lbs. per Used Residual pH
I Per Day I Lbs. 24 Hrs. Qts. mg/I
~1: 0.55 2 0.7
r-}t 0.45 0.7
3 I 0.60 0.7
41 0.53 2 0.8
5 0.68 2 0.7
6 0.71 0.7
7 0.65 0.8
8 0.56 0.8
9 0.34 4 0.8
I 10 0.43 0.8
i 11 I 0.57! 0.8
i 12 I 0.60 0.8
13 0.60 0.8
14 0.33 0.8
i 15 0.55 0.7
! 16 0.43 2 0.7
17 0.67 0.7
i 18L-1.~_t-- 4 0.7
I 1 9 0 . 96 : I 0.7
i 20 i 0.80 I - ~ 0.7
~. 0.39 I 0.7
r1f I 1.55 2 0.7
23 3.92 4 0.7
I 24 4.03 4 0.7
25 1.31 2 0.7
26 4.32 2 0.7
27 7.35 8 0.4
28 7.81 8 0.9
r 29 6.05 6 0.9
30 6.22 10 0.7
I 31 - I
~Total~~ ! 62 22.0
iAvg. I 2.30 2.07 [ 0.70
I
Rep t>rted ~~~fmOI, Inc.
~
Title: Operator
JUL 1 4 2010
TOWN OF WAPPINGER
TOWN CLERK
Population served: 25
Number of required routine sample 1
Number of actual routine samples 1
Does a M&AR violation exist? NO
If yes, check reason(s) below:
_ Actual number of samples fewer than required.
_ Failure to analyze for Ecoli if there was a
positive result for total coliforms from routine, repeat or
high turbidity (hiturb) sample?
_ Failure to analyze repeat samples.
Does an MCL violation exist? NO
If yes, check reason(s) below:
_ Two or more positive total coliform samples for
systems collecting fewer than 40 samples (routine, repeat
or hiturb) per month.
_ More than 5% positive total coliform samples for
systems collecting 40 or more samples (routine, repeat or
hiturb) per month.
_ When a positive total Coliform sample is positive
for Ecoli and a repeat Total Coliform sample is positive,
OR, when a positive Total Coliform sample is negative for
Ecoli, but the repeat Total Coliform sample is positive and
also is positive for E.coli.
. Must collect a minimum of 5 routine samples the month
following a repeat sample collection.
Date: ~j, 2//0
~.~t)---'-
Grade Level: IIA
Cert. No. 12947
ENVIRONMENTAL LABWORKS, INC.
BonLE NU'-A8ER
RECEIVED JUN
BACTERIOLOGICAL EXAMINATION OF WATER
po. Box 733, Marlboro, New York 12542
(845) 236-7823
Fax (845) 236-3911
ELAP 10# 10824
9 2010
COlLECTED BY
SOURCE OF WATER
{.)e ((
TELEPHONE #
CHLORINE RES. ppm () 7
/330':<1 '
REPORT TO BE MAilED TO
!!. fffVl C)
RESULTS OF EXAMINATION
HPC-SM1892158
TOTAL COlIFOR'-AS /l00ML
ABSENT
COUMl AT35-C E.coli/100Ml
ABSENT
METHOD OF EXAMINATION
TOTAL COllFORMS
SM199223B
REMARKS
INTERPRETATION OF RESULTS
6/7/10 3:35pm LB
WAS
THESE RESULTS INDICATE THAT TilE WATER OF A SATISFACTORY SANITARY QUALITY
IN RESPECT TO THE ABOVE TEST, WHEN THE SAM!' E WAS ANALYZED
REPORTED BY
DATE
6-8-10