Tall Trees
Water Systems Operation Report
Microbiological Sam pie Results
Submitted By: CAMO Pollution Control, Inc.
1610 Route 376
Wappingers Falls, New York 12590
Name of Public Water System Program Code Federal Reporting MonthNear
Tall Trees Water 100 1302809 January 2011
Location:
TOWN OF WAPPINGER
County:
DUTCHESS
Source of Supply:
If surface, is filtration provided?
Did an emergency occur in any part of the water system?
Does the system have a disinfection waiver?
\ Ground
I~~
CHLORINATION
Amount of Gaseo US Liquid
Treated Chlorine Hypo- Free
Water Weight of Used chlorite Chlorine
Date 1,000 Gals. Cylinder Lbs. per Used Residual pH
Per Day Lbs. 24 Hrs. Qts. mgll
1 18.32 24 1.0
2 19.43 28 0.8
3 18.19 20 0.8
4 16.08 20 0.8
5 17.08 24 0.9
6 18.53 28 1.0
7 15.19 16 1.0
8 17.56 32 1.0
9 20.86 28 1.0
10 14.81 16 1.0
11 12.64 12 1.1
12 21.54 32 1.1
13 18.28 20 1.0
14 12.62 16 1.0
15 17.53 20 1.0
16 22.64 20 1.0
17 17.29 20 1.0
18 19.76 20 1.1
19 13.37 16 1.1
20 17.93 24 1.2
21 13.71 16 1.2
22 18.93 24 1.1
23 20.75 8 1.2
24 16.97 28 1.2
25 17.35 20 1.1
26 15.92 20 1.3
27 16.90 20 1.3
28 17.18 24 1.2
29 15.20 16 1.2
30 22.70 32 1.2
31 17.44 20 1.2
Total 542.70 664 33
Avg. 17.51 21.4 1.1
Reported by: CAM~i~&~~[Q) I
Title: Operator ,~
FEB 1 -5 2011
TOWN OF WAPPINGER
TOWN CLERK
population served: 251
Number of required routine samplE 1
Number of actual routine samples 1
Does a M&AR violation exist? NO
If yes, check reason(s) below:
_ Actual number of samples fewer than required.
,:"'h_ i i
_ Failure to a'1a1yze for E.coli if there was a
positive result for total coliforms from routine, repeat or
high turbidity (hiturb) sample?
_ Failure to analyze repeat samples.
Does an MCL violation exist? NO
If yes, check reason(s) below:
_ Two or more positive total coliform samples for
systems collecting fewer than 40 samples (routine, repeat
or hiturb) per month.
_ More than 5% positive total coliform samples for
systems collecting 40 or more samples (routine, repeat or
hiturb) per month.
_ When a positive total Coliform sample is positive
for E.coli and a repeat Total Coliform sample is positive,
OR, when a positive Total Coliform sample is negative for
E.coli, but the repeat Total Coliform sample is positive and
also is positive for E.coli.
. Must collect a minimum of 5 routine samples the month
following a repeat sample collection.
Date: 1./ gill
,
~ .\'~ ----
Grade Level: IIA
Cert.No. 12947
----..
ENVIRONMENTAL LABWORKS, INC.
P.O. Box 733, Marlboro, New York 12542
(845) 236-7823
Fax (845) 236-3911
ELAP 10# 10824
RECEIVED JAN 1 3 2011
BACTERIOLOGICAL EXAMINATION OF WATER
PWS 10# _
/36;(.ro
RESULTS FOR LAB USE ONLY
CHLORINE RES. ppm /,6
'?5 'I
NAl.4E ANo.OR LOCATIONS OF WATER SOURCE:
REPORT TO BE MAILED TO
(2 ttl-W\O
TIlESE RESULTS INDICATE THAT THE WATER WAS OF A SATISFACfORY SANITARY QUALITY
IN RESPECT TO THE ABOVE TEST, WHEN THE SAMPLE WAS ANALYZED
REPORTED BY
~ttt~\1c1V
DATE
1-11-11