Wappinger Emergency Services
Water Systems Operation Report
Microbiological Sam pie Results
Submitted By: CAMO Pollution Control, Inc.
1610 Route 376
Wappingers Falls, New York 12590
Program Code Federal Reporting MonthlYear
[Name of Public Water System
Wappingers Emergency Services
105
Location:
TOWN OF WAPPINGER
Source of Supply:
If surface, is filtration provided?
Did an emergency occur in any part of the water system?
Does the system have a disinfection waiver?
CHLORINATION
Amount of Gaseous Liquid
Treated Chlorine Hypo- Free
Water Weight of Used chlorite Chlorine
Date 1,000 Gals. Cylinder Lbs. per Used Residual pH
Per Day Lbs. 24 Hrs. qts mg/l
1 0.43 2 0.5
2
3
i-----4- 0.36 2 0.4
5 0.19 2 0.4
6 0.19 2 0.3
7 0.32 2 0.3
8 0.53 0.3
9
10
11 0.22 . 2 0.2
12 0.24 0.2
13 0.20 2 1.0
14 0.32 1.0
15 0.49 2 1.0
16
17
18 0.25 2 0.5
19 0.23 4 0.5
20 0.30 2 0.8
21 0.67 4 1.8
22
23
24
25 0.28 1.4
26 0.34 2 1.4
27 0.58 2 1.4
28 0.23 1.4
29 0.58 4 1.0
30 ..
31
Total 6.95 36 I 16
Avg. 0.2 1.2 I 0.9
Reported by: CAMO Pollution Control, Inc.
Title: Operator
1330192
April
2011
-~--
County:
DUTCHESS
Ground
No
No
No
Population served: 25
Number of required routine sample 1
Number of actual routine samples 1
Does a M&AR violation exist? NO
If yes, check reason(s) below:
_ Actual number of samples fewer than required.
_ Failure to analyze for E.coli if there was a
positive result for total coliforms from routine, repeat or
high turbidity (hiturb) sample?
_ Failure to analyze repeat samples.
Does an MCL violation exist? NO
If yes, check reason(s) below:
_ Two or more positive total coliform samples for
systems collecting fewer than 40 samples (routine, repeat
or hiturb) per month.
_ More than 5% positive total coliform samples for
systems collecting 40 or more samples (routine, repeat or
hitu rb) per month.
_ When a positive total Coliform sample is positive
for E.coli and a repeat Total Coliform sample is positive,
OR, when a positive Total Coliform sample is negative for
E.coli, but the repeat Total Coliform sample is positive and
also is positive for E.coli.
. Must collect a minimum of 5 routine samples the month
following a repeat sample collection.
Date: <"</0;) III
(52- \~...--
Grade Level: IIA
Cert. No. 12947
ENVIRONMENTAL LABWORKS, INC.
RECEIVED APR 1 4 2011
BACTERIOLOGICAL EXAMINA liON OF W A TEA
PO Box 733, Marlboro, New York 12542
(845) 236-7823
Fax (845) 236-3911
ELAP 10# 10824
~-30 '0,;(
RESULTS FOR LAB USE ONLY
CHLORINE RES ppm~
TELEPHONE #
NAlJE ANo.OR lATiONS Of WATER SOURCE:
-;
REPORT TO BE lAAllED TO
111c" /2 a en G v.
~~ t/C.,
RESULTS OF EXAMINATION
HPC-SM1892158
TOTAL COlI~ORlAS I l00t.4L
METHOD OF EXAMINATION RElAARKS
TOTAL COLI FORMS
SM19 92238 ~/]_2 3pn TJB
Date_Time _Analyzed_
iiHSGN':2
COUML AT35-C Ecoli/100ML
L'LHSGtr.::'
INTERPRETATION OF RESULTS
THESE RESULTS INDICATE THAT THE WATER Hi\S OF ^ SATISFACTORY SANITARY QUALITY
IN RESPECT TO THE ABOVE TEST, WHEN THE SAMPLE WAS ANALYZED
REPORTED BY
DATE
L1 /:.3/20:'.:'.