Tall Trees
Submitted By: CAMO Pollution Control, Inc.
1610 Route 376
Wappingers Falls, New York 12590
Federal I Reporting MonthNearl
1302809 I July ~_~011 J
Water Systems Operation Report
Microbiological Sam pie Results
Name of Public Water System
Program Code
Tall Trees Water
100
Location:
TOWN OF WAPPINGER
Source of Supply:
If surface, is filtration provided?
Did an emergency occur in any part of the water system?
Does the system have a disinfection waiver?
CHLORINATION
Amount of Gaseous Liquid
Treated Chlorine Hypo- Free
Water Weight of Used chlorite Chlorine
Date 1,000 Gals. Cylinder Lbs. per Used Residual pH
Per Day Lbs. 24 Hrs. Qts. mg/l
1 18.20 20 1.1
-
2 26.43 28 1.0
3 15.24 24 1.0
4 25.49 28 0.8
5 21.72 20 1.0
6 18.88 20 1.0
7 18.80 20 1.0
8 17.68 20 1.1
9 25.46 28 1.0
>-W' ---20.64 28 0.9
11 19.52 20 1.0
12 26.00 1.0
13 19.40 2 0.3
14 25.94 28 0.8
15 28.92 32 0.7
f---- - 28 0.6
16 19.31
17 26.98 28 0.7
18 23.09 20 0.7
19 18.51 16 0.8
20 26.30 28 1.0
21 24.46 - 20 1.0
22 28.69 28 1.0
23 23.92 28 1.0
24 28.07 28 1.0
25 20.84 20 1.0
26 16.89 12 1.0
27 20.08 16 0.5
28 17.39 16 0.8
29 21.75 20 0.9
30 28.30 24 0.9
1--- 24 0.8
31 20.65
Total 693.55 674 27
Avg. 22.43 21.7 0.9
Reported by:
Title:
Olluti7FHr!OI, ne.
or D ((;~llW~ltJJ
County:
DUTCHESS
Ground
No
No
No
Population served: 251
Number of required routine sample 1
Number of actual routine samples 1
Does a M&AR violation exist? NO
If yes, check reason(s) below:
_ Actual number of samples fewer than required.
_ Failure to analyze for E.coli if there was a
positive result for total coliforms from routine, repeat or
high turbidity (hiturb) sample?
_ Failure to analyze repeat samples.
Does an MCL violation exist? NO
If yes, check reason(s) below:
_ Two or more positive total coliform samples for
systems collecting fewer than 40 samples (routine. repeat
or hiturb) per month.
_ More than 5% positive total coliform samples for
systems collecting 40 or more samples (routine, repeat or
hiturb) per month.
_ When a positive total Coliform sample is positive
for E.coli and a repeat Total Coliform sample is positive,
OR. when a positive Total Coliform sample is negative for
E.coli. but the repeat Total Coliform sample is positive and
also is positive for E.coli.
* Must collect a minimum of 5 routine samples the month
following a repeat sample collection.
Date:
<;;/'ill'
I
Grade Level: IIA
Cert. No. 12947
AUG 11 20"
TO~N OF WAPPINGER
, OWN CLERK
ENVIRONMENTAL LABWORKS, INC.
PO Box 733, Mar1boro, New YorX 12542
(845) 236-7823
Fax (845) 236-3911
ELAP 10# 10824
RECEIVED JUL 1 4 2D11
BonLE NU"'ilER
D(\~\ \l,-'
BACTERIOLOGICAL EXAMINATION OF WATER
PWS 10# /30 ;;18' 0<')
RESULTS FOR LAB USE ONLY
CHLORINE RES ppm~
COlLECTED BY
PAIVA TE SUPPLY 0
TELEPHONE #
NAME ANo.OR LOCATiONS OF WATER SOURCE:
--I' e Ie
REPORT TO BE MAILED TO
W~. e/C
HPC-SM1892158
TOTAL COlIFORMS 1100ML
l\BSENT
METHOD OF EXAMINATION REMARKS
TOTAL COL/FORMS
SM1992238 7/:_2/:_-:' 37 30pm r FL
Date_Time _Analyzed_
INTERPRETATION OF RESULTS
COUML AT35-C E.coli/100ML
IJ3SEtJ'.::'
HAS
THESE RESULTS INDICATF. THATTHE WATER OF A SATISFAC.'TORY SANITARY QUALITY
IN RESPECT TO THE ABOVE TEST, WHEN THE SAMPLE WAS ANALYZED
REPORTED BY
~lte{(iTltie
DATE
7 - :_3- ~_~_