Tall Trees Water
Water Systems Operation Report
Microbiological Sam pie Results
Submitted By: CAMO Pollution Control, Inc.
1610 Route 376
Wappingers Falls, New York 12590
Name of Public Water System Program Code Federal Reporting MonthlYear
Tall Trees Water 100 1302809 Novem ber 2011
Location:
TOWN OF WAPPINGER
County:
DUTCHESS
Source of Supply:
If surface, is filtration provided?
Did an emergency occur in any part of the water system?
Does the system have a disinfection waiver?
1,120 31
r:~c 1 1.0
I /D)~ - , / I
CAMO Poilu on C~/gi(;~DW'~lI:>> --, Date: I::? I&> '1/
Operator I \() ~ ~ _ ~
DEe 08 2011 /U '
TOWN OF W
1 ToW APPINGER
~ CLERk
-
Amount of
Treated
Water
Date 1,000 Gals.
Per Day
1 18.95
2 20.90
3 20.20
4 17.82
5 16.64
6 21.49
7 20.73
8 17.04
9 19.19
10 15.00
11 19.00
12 17.95
13 22.28
14 20.30
15 19.47
16 17.62
17 17.60
18 21.16
19 15.61
20 20.53
21 21.56
22 18.12
23 18.24
24 23.15
25 21.69
26 18.20
27 23.14
28 21.33
29 16.93
30 21.38
31
Total 583.22
Avg. 19.44
Reported by:
Title:
CHLORINATION
Gaseous Liquid
Chlorine Hypo-
Used chlorite
Lbs, per Used
24 Hrs. Qts.
40
40
40
32
40
40
32
20
40
40
52
52
52
28
28
28
28
36
28
28
40
32
32
40
44
40
40
40
40
48
Weight of
Cylinder
Lbs,
Free
Chlorine
Residual
mg/l
1.1
1.1
1.0
1.1
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.2
1.1
1.0
1.0
1.1
1.0
1.3
1.2
1.0
1.0
1.0
1.0
0.9
1.1
1.0
1.1
1.1
Grouncf
No
No
No
Population served: 251
Number of required routine samplE 1
pH
Number of actual routine samples 1
Does a M&AR violation exist? NO
If yes, check reason(s) below:
_ Actual number of samples fewer than required,
_ Failure to analyze for E.coli if there was a
positive result for total coliforms from routine, repeat or
high turbidity (hiturb) sample?
_ Failure to analyze repeat samples.
Does an MCL violation exist? NO
If yes, check reason(s) below:
_ Two or more positive total coliform samples for
systems collecting fewer than 40 samples (routine, repeat
or hiturb) per month.
_ More than 5% positive total coliform samples for
systems collecting 40 or more samples (routine, repeat or
hiturb) per month.
_ When a positive total Coliform sample is positive
for E.coli and a repeat Total Coliform sample is positive,
OR, when a positive Total Coliform sample is negative for
E.coli, but the repeat Total Coliform sample is positive and
also is positive for E.coli.
* Must collect a minimum of 5 routine samples the month
following a repeat sample collection.
Grade Level: IIA
Cert. No. 12947
-.J
Distribution System Analytical Results
Sampling Date of Sample Total Coliform E.coli Free CI- Raw
Location Sample Type Positive Positive Residual Turbidity
(1,2,3)* mg/L NTU
23 Amhurst 11/15/11 1 Yes No Yes No 0.8 . - -
Yes No Yes No - - - -
Yes No Yes No - - - -
Yes No Yes No - - - -
Yes No Yes No - - - -
Yes No Yes No - - - -
Yes No Yes No - - - -
Yes No Yes No - - - -
Yes No Yes No - - - -
Yes No Yes No - - - -
Yes No Yes No - - - -
Yes No Yes No - - - -
Yes No Yes No - - - -
Yes No Yes No - - - -
Yes No Yes No - - - -
Yes No Yes No - - - -
Yes No Yes No - - - -
Yes No Yes No - - - -
Yes No Yes No - - - -
*1 = Routine sample 2 = Repeat sample 3 = Hiturb sample
COMMENTS and/or REMARKS
ENVIRONMENTAL LABWORKS, INC.
P.O. Box 733, Marlboro, New Yorl< 12542
(845) 236-7823
Fax (845) 236-3911
ELAP 10# 10824
BACTERIOLOGICAL EXAMINATION OF W A TEA
RECEIVED NOV 1 '7 ZDl1
SOURCE OF WATER
tJe/l
TELEPHONE #
g.
REPORT TO BE MAILED TO
WAn
THESE REsULTS INDICATETHATTHE WATER .~. OF A SATISFACfORY SANITARY QUALITY
IN RESPECT TO THE ABOVE TEST, WHEN THE SAMPLE WAS ANALYZED
REPORTED BY
5i'l~letet
DATE
i'V -~rG--.1.]_