Wappingers Emergency Services
.
.
Water Systems Operation Report
Microbiological Sam pie Results
Submitted By: CAMO Pollution Control, Inc.
1610 Route 376
Wappingers Falls, New York 12590
Name of Public Water System Program Code Federal Reporting MonthlYear
Wappingers Emergency Services 105 1330192 January _. 2012
Location:
TOWN OF WAPPINGER
Source of Supply:
If surface, is filtration provided?
Did an emergency occur in any part of the water system?
Does the system have a disinfection waiver?
CHLORINATION
Amount of Gaseous Liquid
Treated Chlorine Hypo- Free
Water Weight of Used chlorite Chlorine
Date 1,000 Gals. Cylinder Lbs.per Used Residual pH
Per Day Lbs. 24 Hrs. qts mg/l
1
2
3 0.14 2 0.4
4 0.24 0.7
5 0.35 2 0.8
6 2.96 16 0.7
7
8
9 0.62 2 0.4
10 0.24 0.4
11 0.30 4 0.4
12 0.28 0.4
13 0.87 4 0.7
14
15
16 0.32 0.7
17 0.62 4 0.7
18 0.36 2 0.7
19 0.27 2 0.7
20 0.93 4 0.7
21
22
23 0.37 2 0.7
24 0.27 2 0.7
25 0.32 0.7
26 0.39 2 0.7
27 1.06 4 0.7
28
29
30 0.50 2 0.5
31 0.24 2 0.5
Total 11.65 56 I 13
Avg. 0.4 1.8 r 0.4
Reported by:
Title:
CAM Pollution on , .
Ope ator fFd~CG~~~~lI]
County:
DUTCHESS
I Ground
I~~
Population served: 25
Number of required routine sample 1
Number of actual routine samples 1
Does a M&AR violation exist?
If yes, check reason(s) below:
NO
12 ~:~ ~?(j
. .f-; (;:.. jj (
_ Actual number of samples fewer than required.
']12
_ Failure to analyze for E.coli if there was a
positive result for total coliforms from routine, repeat or
high turbidity (hiturb) sample?
_ Failure to analyze repeat samples.
Does an MCL violation exist? NO
If yes, check reason(s) below:
_ Two or more positive total coliform samples for
systems collecting fewer than 40 samples (routine, repeat
or hiturb) per month.
_ More than 5% positive total coliform samples for
systems collecting 40 or more samples (routine, repeat or
hiturb) per month.
. ... . ,~';. ~ i
_ When a positive total Coliform sample is positive
for E.coli and a repeat Total Coliform sample is positive,
OR, when a positive Total Coliform sample is negative for
E.coli, but the repeat Total Coliform sample is positive and
also is positive for E.coli.
. Must collect a minimum of 5 routine samples the month
following a repeat sample collection.
Date:
d /"7 /, Z
.
Grade Level: IIA
Cert. No. 12947
FEB 1 02012
TOWN OF WAPPINGER
__TOW_~.. CLERK
'.' ..----.
Distribution System Analytical Results
Sampling Date of Sample Total Coliform E.coli Free CI- Raw
Location Sample Type Positive Positive Residual Turbidity
(1,2,3)" mg/L NTU
Garage Sink 1/16/12 1 Yes No Yes No 0.6 - -
Yes No Yes No - - - -
Yes No Yes No - - - -
Yes No Yes No - - - -
Yes No Yes No - - - -
Yes No Yes No - - - -
Yes No Yes No - - - -
Yes No Yes No - - - -
Yes No Yes No - - - -
Yes No Yes No - - -
Yes No Yes No - - - -
Yes No Yes No - - - -
Yes No Yes No - - - -
Yes No Yes No - - - -
Yes No Yes No - - - -
Yes No Yes No - - - -
Yes No Yes No - - - -
Yes No Yes No - - - -
Yes No Yes No - - - -
*1 = Routine sample 2 = Repeat sample 3 = Hiturb sample
COMMENTS and/or REMARKS
ENVIRONMENTAL LABWORKS, INC.
P.O. Box 733, Marlboro, New York 12542
(845) 236-7823
Fax (845) 236-3911
ELAP 10# 10824
RECE I fED JAN 1 8 201l
BACTERIOLOGICAL EXAMINATION OF WATER
PWS 10# 3 9
' 301
RESULTS FOR LAB USE ONLY
CHLORINE RES ppm C?, 4>
.~t/t2 ,
PRIVATE SUPPLY 0
REPORT TO BE MAILED TO
CfJ1/v10
ruESE RESULTS INDICATE THAT THE WATER WAS OF A SATISFACTORY SANITARY QUALITY
IN RESPECT TO THE ABOVE TEST, WHEN THE SAMPLE WAS ANALYZED
REPORTED BY ~ ..J -
DATE
1/17/2012