Tall Trees Water
Water Systems Operation Report
Microbiological Sam pie Results
Submitted By: CAMO Pollution Control, Inc.
1610 Route 376
Wappingers Falls, New York 12590
Name of Public Water System Program Code Federal Reporting MontfflYear
Tall Trees Water 100 1302809 April -. 2012
Location:
TOWN OF WAPPINGER
Source of Supply:
If surface, is filtration provided?
Did an emergency occur in any part of the water system?
Does the system have a disinfection waiver?
CHLORINATION
Amount of Gaseous Liquid
Treated Chlorine Hypo- Free
Water Weight of Used chlorite Chlorine
Date 1,000 Gals. Cylinder Lbs. per Used Residual pH
Per Day Lbs. 24 Hrs. Qts. mgll
1 0.00 28 0.8
2 13.06 28 0.8
3 17.66 28 0.8
4 20.15 28 0.8
5 20.47 28 1.0
6 24.20 40 1.0
7 24.49 32 0.8
8 5.69 32 0.4
9 17.14 28 1.2
10 19.45 32 1.1
11 18.37 28 1.1
12 20.94 32 0.8
13 20.80 36 1.1
14 20.73 28 0.6
15 24.72 28 0.8
16 26.53 28 0.7
17 21.42 20 0.7
18 20.88 20 1.0
19 17.98 20 1.0
20 17.49 16 0.8
21 24.33 20 0.9
22 23.50 28 0.8
23 15.53 20 0.9
24 23.24 24 0.8
25 17.58 20 0.9
26 16.24 16 1.0
27 22.41 20 0.8
28 19.76 20 0.7
29 23.70 20 0.8
30 16.53 20 0.8
31
Total 574.99 768 26
Avg. 19.26 25.8 0.9
County:
DUTCHESS
I Ground I~~
Population served: 251
Number of required routine samplE 1
Number of actual routine samples 1
Does a M&AR violation exist?
If yes, check reason(s) below:
NO
~ 12C,DO
;q~r{C::'I~
_ Actual number of samples fewer than required.
"'. 20'\2
_ Failure to analyze for E.coli if there was a
positive result for total coliforms from routine, repeat or
high turbidity (hilurb) sample?
_ Failure to analyze repeat samples.
Does an MCL violation exist? NO
If yes, check reason(s) below:
I coliform samples for
~~:JFdre:~SWlit5)ea
More than 5% PrjliliY9 tQtal10liform samples fo.~ .
system collecting 40 or A~M+lsarf,pli; ~1i2e, repeat or ".
hiturb) rTOWN OF WAPPINGE~'" :-"",
When a'l'@WN>liet R ositive
for E.coli and a repea . . 've
OR, when a positive Total Coliform sample is negative for'
E.coli, but the repeat Total Coliform sample is positive and
also is positive for E.coli.
:? :~.: '~,1 ()
2iJ'j?
. Must collect a minimum of 5 routine samples the month
fOllowing a repeat sample collection.
Reported by: CAMO Pollution Control, Inc.
Date: 5/, /1 Z.
I
6J~",<-
Title: Operator
Grade Level: IIA
Cert.No. 12947
" :-.~/ ~;':'
, ~.: .,';,
....:...,
'l!
ENVIRONMENTAL LABWORKS, INC.
P.O. Box 733, Marlboro, New York 12542
(845) 236-7823
Fax (845) 236-3911
ELAP 10# 10824
HECEl VEn APR 1 8 2012
COlLECTED BY ...----
J..)
EXACT COLLECTION POINT ___
/0 e. -0 I
NAME ANQ.OR LOCATIONS OF WATER SOURCE:
..--.--
PRIVATE SUPPLYQ
REPORT TO BE MAIlED TO
PWS 10#
)3 C>~1i Oq
RESULTS FOR LAB USE ONLY
CHLORINE RES. ppmO .8'
BACTERIOLOGICAL EXAMINATION OF WATER
HPC-SM1892158
TOTAl COlIFORMS 1100Ml
METHOD OF EXAMINATION REMARKS
TOTAL COLIFORMS
SM1992238
4/1 n 3: 5,,5offi_.. NP
Date lime _I"\nalyz"",_
INTERPRETATION OF RESULTS
ABSENT
COUMLAT35-C E.coli/100ML
ABSENT
THESE RESULTS INDICATETHATTHE WATER WA~ OF A SATISFACTORY SANITARY QUALITY
IN RESPECT TO THE ABOVE TEST, WHEN mE SAMPLE WAS ANALYZED
REPORTED BY
DATE
4/17/2012